Helical Anchor Design

ECP Helical Torque Anchors™ are engineered for high-load, reliable performance in a wide range of soil conditions. The tables below provide key design capacities and installation guidance for ECP helical anchor systems.

Capacities of ECP Helical Torque Anchors™

Shaft Size Installation Torque Factor (k) Axial Compression Load Limit Ultimate-Limit Tension Strength Useable Torsional Strength Practical Load Limit Based Torsional Strength
1-1/2″ Square Bar 9 – 11 70,000 lb. 70,000 lb. 7,500 ft-lb Load limited to the rated capacity of the attachments and the lateral soil strength against the shaft
1-3/4″ Square Bar 9 – 11 100,000 lb. 100,000 lb. 10,000 ft-lb
2″ Square Bar 10 – 12 200,000 lb. 200,000 lb. 23,000 ft-lb
2-7/8″ Tubular – 0.262″ Wall 8 – 9 100,000 lb. 100,000 lb. 9,500 ft-lb 80,000 lb
3-1/2″ Tubular – 0.300″ Wall 7 – 8 115,000 lb. 120,000 lb. 13,000 ft-lb 97,000 lb
4-1/2″ Tubular – 0.337″ Wall 6 – 7 160,000 lb. 160,000 lb. 22,000 ft-lb 143,000 lb
*See IBC Section 2117

Projected Areas* of Helical Torque Anchor™ Plates

Helical Plate 6″ Dia. 8″ Dia. 10″ Dia. 12″ Dia. 14″ Dia. 16″ Dia.
Shaft Projected Area – ft2
1-1/2″ Sq. 0.181 0.333 0.530 0.770 1.053 1.381
1-3/4″ Sq. 0.175 0.328 0.524 0.764 1.048 1.375
2-1/4″ Sq. 0.161 0.314 0.510 0.750 1.034 1.361
2-7/8″ Dia 0.151 0.304 0.500 0.740 1.024 1.351
3-1/2″ Dia 0.130 0.282 0.478 0.719 1.002 1.329
4-1/2″ Dia 0.086 0.239 0.435 0.675 0.959 1.286
*Factor area is a theoretical projected area of the helix/plate. Actual surface area can be as much as 10% of theoretical area.

Allowable Mechanical Helical Plate Capacities

6″ through 14″ Diameter Plates
Helical Plate Thickness Average Ultimate Load Average Working Load
3/8″ 40,000 lb 20,000 lb
1/2″ 50,000 lb 25,000 lb
16″ Diameter Plate
1/2″ 40,000 lb 20,000 lb
Note: Assumptions for K 1 (1.0″ “actual” pitch), anchor in clean, loose, free-draining sand (no clay). Performance may be reduced if anchors are loaded in soil conditions with which the helix(es) will not achieve full bearing resistance.

Installation Torque Factor "k"

Torque Anchor™ Type Estimated Empirical Torque Factor Range – “k”
1-1/2″ Solid Square Bar 9 – 11
1-3/4″ Solid Square Bar 9 – 11
2-1/4″ Solid Square Bar 10 – 12
2-7/8″ Diameter Tubular 8 – 9
3-1/2″ Diameter Tubular 7 – 8
4-1/2″ Diameter Tubular 6 – 7
Important:
Installation torque is required to achieve the anchor’s ultimate capacity. Installation in hard dense, cobbles or mixed, oversize conditions may require field verification.
K = Installation Torque Factor Load
D = Anchor Shaft Diameter (inches)
HP = Helix Pitch (inches)
T = Installation Torque (in-lb)
D = Helix Outside Diameter (inches)
P = Projected Horizontal Area of the Helix (in²)
F = Projected Horizontal Area of the Plate (in³)
*Helix (s) and/or plate sizes can impact installation torque range; deviations see testing handbook.